← Back to SEL-2740S L2S Security Technical Implementation Guide

V-92281

CAT II (Medium)

The SEL-2740S must be configured with backup flows for all host and switch flows to ensure proper failover scheme is in place for the network.

Rule ID

SV-102369r1_rule

STIG

SEL-2740S L2S Security Technical Implementation Guide

Version

V1R1

CCIs

CCI-000366

Discussion

The SEL-2740S must be capable of multiple fast failover, backup and in cases isolation of the traffic from a detected threat in the system.

Check Content

Review the SEL-2740S flow rules to ensure each flow has a Fast Failover Group configured.

If the switch is not configured to provide backup flows, this is a finding.

Fix Text

To configure a Fast Failover Group for a given flow, do the following:

1. Log on to OTSDN Controller using Permission Level 3.
2. Under Group Entry General settings, select "Group ID" and "Group Type" as "Fast Failover".
3. Select appropriate number of Action Buckets dependent upon use case.
4. Determine valid watch port or group, and select supported actions.
5. Click "Submit".