V-92279

CAT II (Medium)

The SEL-2740S must be configured to capture all packets without flow rule match criteria.

Rule ID

SV-102367r1_rule

STIG

SEL-2740S L2S Security Technical Implementation Guide

Version

V1R1

CCIs

CCI-000366

Discussion

The OTSDN switch must be capable of capturing frames that are not engineered to be in the network and send them to a Security Information and Event Manager (SIEM) or midpoint sensor for analysis.

Check Content

Review the SEL-2740S to ensure that the "no match criteria" rule is set to capture the packet for analysis as a possible injection or intrusion. 

If the SEL-2740S is not configured to with the "no match criteria" rules for the Security Information and Event Manager (SIEM), this is a finding.

Fix Text

To configure to capture all packets without flow rule match criteria, do the following:
1. Log on to OTSDN Controller using Permission Level 3.
2. Click "Flow Entries" in Navigation Menu.
3. Click "Add Flow" button.
4. Enter a "no match" flow rule for given ports.
5. Click "Submit".